TECHNICAL DATA
Detector type: UG-7-A6O-24V UG-7-A6O-120V
Power supply voltage:
24V DC (-5/+20%)
24V AC (±10%) 50-60 Hz
110-120V AC 50-60 Hz
Reset time (by power down): 1 sec. max.
Power up time: 1 min.
Sensitivity test: Nominal sensitivity 0,96-1,20%/ft
Max. standby current: 42 mA 82 mA 31 mA (at 120V AC)
Max. alarm current: 83 mA 145 mA 42 mA (at 120V AC)
Link current: 5 mA
Total max. auxiliary current output on terminals 2 and 5:
Without linked detectors: 30 mA
With linked detectors: 25 mA
Operating temperature: 32°F to 100°F (0°C to 38°C)
Storage temperature: -22°F to 158°F (-30°C to 70°C)
Humidity: 0 to 95% RH
Duct air velocity range: 100 - 4000 ft/min (0,5 - 20,32 m/s)
Dimensions (LxWxD): 9,49x7,68x2,68" (241x195x68 mm)
Weigh: 1,04 kg
Air sampling tube: Aluminium.
Hole diameter 1,5” (38 mm).
ORDERING EXAMPLE
Item code Designation
UG-7-A6O-24V Duct smoke detector 24V AC/DC
UG-7-A6O-120V Duct smoke detector 120V AC
ST1 Sampling tube length: 1 ft (0.3 m)
ST2 Sampling tube length: 2 ft (0.6 m)
ST5 Sampling tube length: 5 ft (1.5 m)
ST9 Sampling tube length: 9 ft (2.8 m)
UG-7-DV-T2 Diverter
Onrion LLC
93 South Railroad Avenue, STE C Bergenfield, 07621-2352, New Jersey, USA
Phone:
+1 973 536 2331
Fax:
+1 973 302 5583
E-mail:
sales@onrion.com