Producto: 97/DF500-Z2
País: Estados Unidos
Descripción: Original Spare Part
Techical specification: Type 97/DF500-Z2
Drawing No. 2.01.277.0.0
Electrical data
Total power (kW) 500
Tolerance of power (%) +5/ -10
Supply voltage (V) 400
Connection Delta
Protection mode IP 54
Operationg Conditions
Medium Thermal Oil
Flow rate 72000
Unit kg/h
Inlet temperature (°C) 220
Outlet temperature (°C) 231
zul. min Temp. TS (°C) 0
zul. max Temp. TS (°C) 300
Operating pressure (bar g) 5
maximum permissible pressure PS (bar g 6
Test pressure 9
Mounting position horizontal
Design Code/Acceptance DGRL Kat. IV / TÜV Nord
Design code / Approval: AD2000
in addition: Design calc. acc. ASME VIII Div.1
(but materials + manufacturing acc. AD2000)
mechanical design
Heating element Tubular heating elements
Diameter (mm) 11,5
Material of heating element 1.4571
Surface load (W/cm²) 3,2
Quantity of heating elements 90
Heating elements eingeschweißt
Immersion length of heating elements 2.650
unheated length (mm) 250
. 4 pcs. Dual-Thermocouples, 2 x NiCr-Ni, Type "K"
. (2 pcs. in each immersion heater)
. (for connection to intrinsic safe circuit Ex ic)
Durchmesser Umlenkblech 198
Sealing GISO
Nominal size / Nominal diameter (DN) 8"
Pressure stage (bar) 300 lbs
Material P250GH (1.0460)
Type of spacers Distanzscheibe Rautenform
Number of Spacers 12
Connection box 500 x 500 x 210, 1.4301
Quantity of cable glands 8
Cable gland 6 x M63x1,5, 2 x M16x1,5
Sealing graphite on stainless steel insert
Heating Vessel
Material of vessel carbon steel,coated temperature resistent
Inspections / Tests
. ----------------------
. 1) The heater needs to be operated with a suitable
. electric control unit only. Temperature controll,
. temperature limitation and flow monitoring need
. to be implemented propperly.
. 2) The thermocouples are for temperature limi-
. tation purpose. They need to get connected
. through intrinsic safe circuits (Ex ic) to
. electronic safety temperature limites (ESTBs)
. inside of the electronic control unit.
. The trip points of this ESTBs need to be adjusted
. to a maximum temperature of 300°C and locked.
. The control unit needs to initiate an automatic
. power shutdown in case of ESTB tripped.
. 3) The equippment is marked as T. to indicate that
. additional measures are necessary in order to
. certify for a temperatur class. In this case, the
. temperature limitation need to get implemented
. propperly by the electric control unit and a
. thermal piece test needs to get performed
. under operation conditions.
. 4) Thermal piece test is not included in the
. price. We can offer it separately if reed.
Condición: Nuevo (sin uso)
Proporcionamos productos de alta calidad de Schniewindt que se puede utilizar para recuperar su equipo roto.
Un miembro de nuestros expertos obtendrá los precios más baratos para los productos de 97/DF500-Z2 Original Spare Part en Estados Unidos.
Los productos de Schniewindt son líderes en esta área. Alta calidad con precio razonable.
No pierda su tiempo buscando en fuentes diferentes piezas de repuesto de diferentes proveedores, en lugar de pedirnos.
Nuestra empresa no es un distribuidor oficial de Schniewindt, pero estamos vendiendo sus productos a precios competitivos.
Compre el producto original de Schniewindt - 97/DF500-Z2 Original Spare Part en Estados Unidos a precios razonables.
No dude en convertirse en uno de nuestros clientes, no se arrepentirá!
Contáctenos por correo electrónico o complete nuestro solicitud de cotización.
Nuestra empresa no es un distribuidor o representante oficial de esa marca.